List of Property Enumeration Sets for MV Objects
Object Name
Object
Type and
instance
BACnet Index Text Default value
1 Local Occupancy
2 Occupied
Occupancy
Command
MV12
3 Unoccupied
Local Occupancy
1 Off
2 Auto
3 Cool
4 Heat
System Mode HPU MV13
5 Emergency
Auto
1 Off
2 Auto
3 Cool
System Mode RTU MV14
4 Heat
Auto
1 On
2 Auto
Fan Mode MV15
3 Smart
Smart
1 Level 0
2 Level 1
Keypad Lockout MV18
3 Level 2
Level 0
1 Occupied
2 Unoccupied
Effective
Occupancy
MV 34
3 Temporary Occupied
Depends on local
occupancy
1 3 CPH
2 4 CPH
3 5 CPH
4 6 CPH
5 7 CPH
Heating CPH MV53
6 8 CPH
4 CPH
1 3 CPH
Cooling CPH MV54
2 4 CPH
4 CPH
1 0 hour
2 1 hour
3 2 hours
4 3 hours
5 4 hours
6 5 hours
7 6 hours
8 7 hours
9 8 hours
10 9 hours
11 10 hours
12 11 hours
Temporary
Occupancy Time
MV61
13 12 hours
3 hours