10
List of Property Value Range Restrictions
Object name
Object Type
and instance
Minimum range
value
Maximum
range value
Default value
Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (50°C) N/A
Outdoor Temperature AV 9 -39°F (-40°C) 121.9°F (50°C) N/A
Room Humidity AV 10 5% 90% N/A
Supply Temperature AI 12 -39.9°F (-40°C) 121.9°F (50°C) N/A
PI Heating demand AV 21 0% 100% 0%
PI Cooling demand AV 22 0% 100% 0%
Occupied Heat Setpoint AV 39 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool Setpoint AV 40 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Stand-by Heat Setpoint AV 41 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Stand-by Cool Setpoint AV 42 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Unoccupied Heat Setpoint AV 43 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Unoccupied Cool Setpoint AV 44 54°F (12°C) 100°F (37.5°C) 80°F (26.5°C)
Password Value AV 56 0 1000 0
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Stand-by Time AV 67 0.5 Hours 24.0 Hours 0.5 Hours
Unoccupied Time AV 68 0.0 Hours 24.0 Hours 0.0 Hours
RH Setpoint AV 45 30% 100% 50%
Dehumidification Hysterisys AV 46 2% 20% 5%
Dehumidification MAX
cooling
AV 47 20% 100% 100%
List of Property Enumeration Sets for BV Objects and BI Objects
Object Name
Object
Type and
instance
Inactive_Text Active_Text Default value
Room Temp Override BV 8 Normal Override Normal
Room Humidity Override BV 11 Normal Override Normal
Dehumidification Lockout BV 13 Disabled Enabled Enabled
AUX Command BV 14 Off On Off
Dehumidification Status BI 23 Off On Off
Aux Status BI 25 Off On Off
BI 1 Status BI 29 Deactivated Activated Deactivated
BI 2 Status BI 30 Deactivated Activated Deactivated
UI 3 Status(*) BI 31 Deactivated Activated Deactivated
Local Motion BI 32 No Motion Motion No Motion
Window Alarm BI 35 Off On Off
Filter Alarm BI 36 Off On Off
Service Alarm BI 37 Off On Off
Menu Scroll BV 49 No Scroll Scroll Active Scroll Active
Auto Mode Enable BV 50 Disabled Enabled Enabled
Temperature Scale BV 51 °C °F °F
Setpoint Type BV 60 Permanent Temporary Permanent
Setpoint Function BV 61 Dual Setpoints Attached
Setpoints
Dual Setpoints
Reheat Time Base BV 64 15 minutes 10 seconds 15 minutes
Auto Fan BV 66 Auto Speed Auto Speed /
Auto Demand
Auto Speed
RH Display BV 70 Disabled Enabled Disabled
Control Type BV 75 On/Off Floating On/Off
Direct/ Reverse Acting BV 78 Direct Acting Reverse Acting Direst Acting
(*) This object will be linked to the value of the ‘UI 3 Configuration’ object.
When the ‘UI 3 Configuration’ object value is 0, 3 or 4, the value will be set
to ‘Deactivated’